- Your one-stop destination for all your HVAC/R needs. Partner with the power of Danfoss
- 82+ years of experience in providing energy efficient and reliable solutions for refrigeration and air conditioning.





























































NeoCharge can be applied to both Nh3 and Co2 air coolers.
It is easy to mount on bottom-, top-, or side-fed systems
and is suitable for stainless steel pipes as well as
carbon-steel galvanized pipes.
Minimum signal required is Cooling ON, OFF and defrost
ON/OFF (in existing system).
In new systems, the EKE450 NeoController can manage
defrost in addition to injection control.














The new Danfoss Intelligent Purger System (IPS) is an automatic,
self-contained operating unit that helps remove non-condensable gases
in a safe and energy-efficient way. This helps maintain optimum
refrigeration capacity and system efficiency, allowing professionals
to achieve maximum system performance.

| Supply voltage | 230V AC, 1ph, 50Hz |
| Current | 3.7 A |
| Power consumption | 1.3 kW |
| Ambient temp, operation | -10°C to +43°C (14°F to 109°F) |
| Ambient temp, transport | -30°C to 55°C (-22°F to 131°F) |
| Enclosure | IP55 |
| Weight | 90 kg (199 lbs) |
| Dimensions (L×W×H) | 1051 x 441 x 703 mm (41.4 x 17.4 x 27.7 inches) |
| Purger refrigerant | R452A 900gram (1 lbs 15.75 oz) |
| System refrigerant | R717 minimum 6 bar (87 psi) |
| Max operating pressure (R717) | 40 bar (580 psi) |
| Operating temperature (R717) | -40°C to +60°C (-40°F to +140°F) |
1°C higher condensing temperature leads to:
| Power consumption of higher stage compressors | = 300 kW |
| Compressor running time per year | = 5000 hrs |
| Measured Subcooling | = 5 K |
| Cost of energy | = INR 10 /kWh |
| Annual kWh of higher stage compressors with NCGs | = 1500000 kWh |
| Annual kWh expenses | = 15 Cr |
| Estimated increase in condensing temperature | = 2 K |
| Estimated % increase in kWh/year | = 6% |
| Annual extra kWh consumption due to NCGs | = 90000 kWh |