Opteon Refrigerants

Chemours has applied its leadership in science and technology to introduce its newest innovation in more environmentally sustainable refrigerants:
The OpteonTM portfolio of low GWP refrigerants.

The OpteonTM Advantage

Performance without compromise
A lasting solution for both efficiency and the environment
Current Low GWP Leading Options
Product GWPa Non Flammable Class 1 Mildly Flammable Class 2L
Product GWPa Product GWPa
HFC-134a 1300 (1430) XP10 (R-513A) 573 (631) YF (R-1234yf) 4 (<1)
HFC-404A 3943 (3922) XP40 (R-449A) 1282 (1397) XL40 (R-454A) 238 (239)
XP44 (R-452A) 1945 (2140)
HFC-410A 1924 (2088) XL41 (R-454B) 467 (466)
XL55 (R-452B) 676 (698)
HCFC-22 1760 (1810) XP20 (R-449C) 1146 (1251) XL20 (R-454C) 146 (148)
HCFC-123 79 (77) XP30 (R-514A) 1
HFC-245fa 1030 MZ(R-1366mzzZ) 9 (2)

a:The AR5 reported GWP values (listed inside the brackets) are presented here for comparison with the AR4 reported values (listed outside the brackets).

FreonTM Refrigerants

Freon 134a

Physical Data | Type
HFC

Chemical Formula
CH2FCF3

ASHRAE Number
R-134a

Molecular Mass
102.03

Boiling Point @ 1 Atmosphere [°F / °C]
-14.9 / -26.06

Critical Temperature [°F / °C]
213.9 / 101.08

Critical Pressure [Psia / kPa] – abs
588.9 / 4060.3

ASHRAE Safety Group Classification
A1

Applications

• Medium- and high-temperature for stationary commercial refrigeration, chiller equipment, and home appliances

• Retrofit existing R-12 refrigeration and air conditioning equipment

Replaces
R-12

Freon 410A

Physical Data | Type
HFC

Chemical Formula
CH2F2 / CHF2CF3

ASHRAE Number
R-410A

Molecular Mass
72.58

Boiling Point @ 1 Atmosphere [°F / °C]
-60.84 / -51.58

Critical Temperature [°F / °C]
161.83 / 72.13

Critical Pressure [Psia / kPa] – abs
714.5 / 4926.1

ASHRAE Safety Group Classification
A1

Applications

• New residential and commercial air conditioning and heat pumps

Replaces
R-22

Freon 404A

Physical Data | Type
HFC

Chemical Formula
CHF2CF3/CH3CF3/CH2FCF3

ASHRAE Number
R-404A

Molecular Mass
97.6

Boiling Point @ 1 Atmosphere [°F / °C]
-51.62 / -46.45

Critical Temperature [°F / °C]
161.73 / 72.07

Critical Pressure [Psia / kPa] – abs
541.2 / 3731.5

ASHRAE Safety Group Classification
A1

Applications

• Commercial refrigeration equipment
• New and existing R-502 equipment

Replaces
R-502

Freon 407C

Physical Data | Type
HFC

Chemical Formula
CH2F2/CHF2CF3/CH2FCF3

ASHRAE Number
R-407C

Molecular Mass
86.2

Boiling Point @ 1 Atmosphere [°F / °C]
-46.4 / -43.56

Critical Temperature [°F / °C]
188.13 / 86.74

Critical Pressure [Psia / kPa] – abs
669.95 / 4619.1

ASHRAE Safety Group Classification
A1

Applications

• New or existing positive displacement equipment

Replaces
R-22

BRANDS